Does Saving Water Cost More Electricity?

Often it does: cooling by evaporation saves electricity but uses water, and cooling without it saves water but uses more electricity, so the two must be judged together.

The Physical World Behind AI, the Tech Innovations library

First published 30 October 2026 Last reviewed 29 October 2026 The Bigger Picture

In most data centre cooling, yes. Evaporating water is a very efficient way to move heat, so systems that use it need less electricity. Systems that avoid evaporation save water but need more electricity, especially in hot weather. Neither choice is right everywhere. The sensible test is to look at energy and water together, in the climate where the data centre sits.

What the evidence says

Lawrence Berkeley National Laboratory's 2024 report on US data centres says water-cooled chillers and other evaporation-based cooling systems are generally more energy efficient than an air-cooled chiller or other waterless systems, and that while air-cooled chillers use no water, they use more energy. It sums up: in many cases, there are tradeoffs between low PUEs and low site WUEs. Microsoft, describing its move to designs without evaporative cooling, says the change will increase its power usage effectiveness, PUE, and calls the result a nominal increase in annual energy use.

Two measures, read together

PUE compares the total energy of the facility with the energy of the computers; closer to 1 means less energy spent on cooling and other overheads. The US Department of Energy notes that data centres with average energy efficiency have a PUE of 2.0, while highly efficient ones approach the theoretical minimum of 1.0. WUE compares the water used on site with the energy of the computers, in litres per kWh. A design can look excellent on one measure and poor on the other, so a single headline number can mislead.

Cooling choiceElectricity for coolingWater used on site
Cooling tower with water-cooled chillersLowerHigher, through evaporation
Free cooling through a cooling towerVery low when the weather allowsHigh, like all evaporative systems
Air-cooled chillers or dry coolersHigher, especially in hot weatherLittle
Closed liquid loop at the chip with dry coolersModerate; liquid moves heat efficientlyLittle

Climate decides the balance

Cool climates allow free cooling with outside air for many hours, which saves both energy and water. In hot and dry places, evaporation saves the most electricity but water is often scarce. In hot and humid places, evaporation works less well. The best design for one site can be the wrong one for another, and the water used to generate the extra electricity belongs in the comparison too.

What is not certain

  • The size of the trade-off depends on the design, the climate and the electricity supply; the table shows directions, not measured values.
  • Off-site water used to generate electricity is often left out of on-site figures, which can make waterless designs look better or worse than they are.

Sources and method

Method: each link was opened on 29 October 2026 and every figure was taken from the page cited beside it. No figure was estimated.